| Parámetro | Valor |
|---|---|
| EAN | 4048879080156 |
| Onda | max. 20 mV eff/rms |
| Zapatillas con clavos | max. 150 mV ss/pp |
| Clase electrónica | 27049002 |
| N.º de artículo: | 85305 |
| Frecuencia | 50...60 Hz |
| Normas | EN 60950-1, EN 61204-3, EN 55022 B |
| Eficiencia | 87% (115 V AC); 88% (230 V AC) |
| Pantalla LED | LED (green) for output voltage |
| Corriente de entrada | 4 A (115 V AC); 2.4 A (230 V AC) |
| Voltaje de entrada | 90...132 V AC/173...264 V AC |
| Corriente de salida | 10 A (+40 °C); 7.5 A (+55 °C) |
| Voltaje de salida | 24 V DC ±1% |
| Unidad de embalaje | 1 |
| Método de montaje | DIN-rail mountable TH35 (EN 60715) |
| Protección de la unidad | Short-circuit and overload protected |
| Humedad relativa | 20...90%, no condensation |
| Rango de temperatura | 0...+40 °C, ...+50 °C derating (storage temperature -20...+85 °C) |
| país natal | CN |
| Producto alternativo: | Product ComparisonINPUT: 90...132 V AC/173...264 V ACOUTPUT: 24 V DCCurrent: 10 AInputInput voltage90...132 V AC/173...264 V ACInput current4 A (115 V AC); 2.4 A (230 V AC)Inrush current after 1 msmax. 20 APrimary fusing externalmax. 20 AFrequency50...60 HzGeneral dataStandardsEN 60950-1, EN 61204-3, EN 55022 BMounting methodDIN-rail mountable TH35 (EN 60715)Efficiency87% (115 V AC); 88% (230 V AC)Relative humidity20...90%, no condensationDimensions H × W × D125×72×125 mmTemperature range0...+40 °C, ...+50 °C derating (storage temperature -20...+85 °C)OutputOutput voltage24 V DC ±1%Output current10 A (+40 °C); 7.5 A (+55 °C)Mains failure bridging timemin. 20 ms (115 V AC); min. 20 ms (230 V AC)Ripplemax. 20 mV eff/rmsUnit protectionShort-circuit and overload protectedSpikesmax. 150 mV ss/ppLED displayLED (green) for output voltageParallel usage/serial usageno/yes (max. 2 units)Commercial datacountry of originCNcustoms tariff number85044090EAN4048879080156eClass27049002Packaging unit1 |
| número de arancel aduanero | 85044090 |
| Dimensiones alto × ancho × profundidad | 125×72×125 mm |
| Fusible primario externo | max. 20 A |
| Corriente de entrada después de 1 ms | max. 20 A |
| Tiempo de puenteo por fallo de red | min. 20 ms (115 V AC); min. 20 ms (230 V AC) |
| Uso paralelo/uso en serie | no/yes (max. 2 units) |