| Parámetro | Valor |
|---|---|
| Serie | Switch-disconnector-fuses - FULOS |
| Montaje | Panel mounting |
| Aprobaciones | KEMA pending |
| Normas | BS88part21988;BSNBNEN60947-3;CEI17-11(Fasc.1039);DINVDE0636Teil1;DINVDE0660Teil1;IEC60269-2-1;IEC60947-1;IEC60947-3;K63B;NBNEN60947-3;NFC63-210;NFC63130;NFC63211;NFEN60269-1 |
| Tipo de fusible | DIN |
| 110 V (CC 23 A 2P) | 1000 A |
| 250 V (CC 23 A 2P) | 1000 A |
| Número de polos | 3P |
| 500 V (CA 21 A/CA 21 B) | 1000 A |
| 500 V (CA 22 A/CA 22 B) | 1000 A |
| 500 V (CA 23 A/CA 23 B) | 1000 A |
| 690 V (CA 21 A/CA 21 B) | 1000 A |
| 690 V (CA 22 A/CA 22 B) | 1000 A |
| 690 V (CA 23 A/CA 23 B) | 1000 A |
| Tipo de Dilos/Fulos | FULOS 4 |
| Tipo de seccionador | Switch-disconnector-fuse |
| ETIM 5.0 (DIMENSIONES) | EC001040 |
| ETIM 6.0 (DIMENSIONES) | EC001040 |
| 400/415 V (CA 21 A/CA 21 B) | 1000 A |
| 400/415 V (CA 22 A/CA 22 B) | 1000 A |
| 400/415 V (CA 23 A/CA 23 B) | 1000 A |
| Peso (ESPECIFICACIONES) | 33 kg |
| Indicación de la posición del contacto | Positive contact position indication |
| Tensión de aislamiento nominal Ui (V) | 1000 V |
| Par máximo en terminales (Nm) | 35 Nm |
| Tensión nominal de funcionamiento Ue (V) | 690 V |
| Potencia nominal a 400 V (kVAR) | 475 kVAr |
| Capacidad del terminal (carril de Cu mm x mm) | Cu-rail 2x50x10 mm |
| Corriente térmica convencional cerrada lthe | 1000 A |
| Tensión nominal soportada al impulso (2000 m) Uimp | 8 kV |
| Corriente térmica convencional encerrada Ithe = Ith | 1000 A;800 A |
| Durabilidad (número de ciclos operativos) eléctrica | 1000 |
| Durabilidad (número de ciclos operativos) mec. (mín.) | 4000 |
| Corriente nominal del condensador S/C Protección de respaldo kA rms a 400 V | 100 kA |
| Corriente nominal del condensador S/C Protección de respaldo kA rms a 415 V | 100 kA |